FramersMath

FramersMath › Headers

Header Size Calculator

Size a door or window header in an exterior bearing wall. Pick what the wall carries, your snow load and building width to get the maximum span and the jack studs needed.

Header

Wall
From your building dept. Under 30 → 30
Measured across the ridge
Header span between jacks
Max header span—
Jack studs required—
Your opening —
Table column used—

Smallest header that works: —

HeaderMax spanJacks
From the 2021 International Residential Code, Table R602.7(1) (same values as the 2018 IRC): girder and header spans for exterior bearing walls, No. 2 grade Douglas fir-larch, hem-fir, southern pine and spruce-pine-fir. Snow load and building width are rounded up to the next table column (the code permits interpolation, which can allow slightly more). Jack studs are per end. Not for interior bearing walls, girder trusses, point loads, LVL or other engineered headers, roofs with a live load over 20 psf, wind or seismic conditions outside IRC limits, or snow loads over 70 psf. Your local code may differ.

⚠ Check all math and verify with a licensed engineer and your local building department before cutting or building. Results are estimates.

Sources: Headers

  1. 2021 International Residential Code, Chapter 6 (Wall Construction)International Code CouncilTable R602.7(1) girder and header spans for exterior bearing walls, with notes on jack studs and the 0.70 unbraced factor.
  2. 2021 Seattle Residential Code, Chapter 6 (PDF reprint of the IRC text)City of SeattleCopy of the 2021 IRC table the values were transcribed from.
  3. 2018 Seattle Residential Code, Chapter 6 (PDF reprint of the 2018 IRC text)City of SeattleSecond copy (2018 IRC) used to cross-check every row; all 75 rows match.

Code tables are copied from the documents above and checked against a second copy where noted. Your local code, its edition and amendments govern. Check all math and verify with a licensed engineer and your building department. See the terms & disclaimer.

How to use the header size calculator

  1. What the header supports: just the roof and ceiling, or floors above too. A center-bearing floor has its joists landing on a center wall or beam. A clear-span floor spans the full width of the house, so the exterior walls carry more of it.
  2. Ground snow load: your building department publishes it. Where it's under 30 psf (and roof live load is 20 psf or less), use 30.
  3. Building width is measured perpendicular to the ridge, which is the direction the rafters or trusses run.
  4. Header size: (2) 2×10 means two 2×10s on edge, normally with 1/2" plywood or OSB between them so the header is as wide as a 2×4 wall.
  5. Braced or not: if cripple studs sit on top of the header instead of joists or rafters bearing on it, the code reduces 2×8, 2×10 and 2×12 header spans to 70%.

Example

A one-story house 24' wide with a 30 psf ground snow load. A (2) 2×10 header in an exterior wall can span 6'-10" with 2 jack studs at each end. Over a 6' opening it works with 10" to spare. A (2) 2×8 only reaches 5'-9", so it falls short.

Jack studs and king studs

Jack (trimmer) studs carry the header down to the plate. The table gives how many are needed at each end. Where it says 1, the code also allows an approved framing anchor to the full-height king stud instead. King studs are full-height studs beside the jacks. The IRC sets how many by opening width in Table R602.7.5.

When to use an engineered header

For long openings like garage doors and big sliders, girder trusses bearing on the header, point loads from posts, or anything outside the table, use an LVL or other engineered header sized by its maker or a licensed engineer.

FAQ

What size header do I need for a 6 foot opening?

In an exterior wall carrying only roof and ceiling, with 30 psf ground snow and a 24' wide building, a (2) 2×10 spans up to 6'-10" with 2 jack studs per end. A (2) 2×8 only spans 5'-9", so it falls short.

How far can a double 2x12 header span?

Carrying roof and ceiling only, with 30 psf snow, a (2) 2×12 spans 10'-7" in a 12' wide building, 8'-1" at 24' and 6'-10" at 36', per IRC Table R602.7(1).

How many jack studs does a header need?

The IRC table lists it for each header, from 1 to 4 per end. Bigger loads and longer spans need more. Where the table says 1, an approved framing anchor to the king stud can replace the jack.

Do interior walls use the same header table?

No. Interior bearing walls use IRC Table R602.7(2), and non-bearing walls don't need a structural header. This calculator only covers exterior bearing walls.

Disclaimer: Results are estimates for planning and layout only. Check all math yourself and verify with a licensed engineer and your local building department before cutting or building. FramersMath is not a substitute for engineered plans, span tables or code review. See the full disclaimer.